Sometimes a contactor can get stuck closed (or “welded on”) when too much current flows through it. This can cause the metal parts inside to fuse together. If the welding is minor, you might be able to fix it. But if it’s severe, the contactor is usually damaged for good.
What Causes a Contactor to Weld?
-
Inrush Current
The most common cause is inrush current—a sudden, very high current that flows when a contactor first connects power to a device with capacitors (like VSDs, motor controllers, chargers, or DC-DC converters).
When a capacitor isn’t charged, it acts like a short circuit. Thousands of amps can flow in just a few millionths of a second. Even though the burst is short and doesn’t use much energy, it’s often enough to weld the contacts.
The problem is usually only noticed later—when the contactor won’t open—and this can make it seem like it wasn’t strong enough to carry regular current, rather than being damaged at turn-on.
Catching this kind of current spike is tough without an oscilloscope. A regular multimeter won’t see it.
A precharge circuit is the best way to avoid this. It limits inrush current by charging the capacitors before the contactor closes. Without it, contactor welding is much more likely.
-
Short Circuit
Another cause—less common but more dramatic—is a short circuit. This usually happens because of a downstream failure. Thousands of amps blast through the contactor, generating intense heat that fuses the contacts.
This sort of welding is easier to spot because it usually sets off a protection device like a fuse or breaker, or damages other nearby components as well.
-
Coil Drive Issues
Some contactors have built-in coil suppression (also called flyback or back-EMF suppression). If they do, you shouldn’t add extra suppression components elsewhere in the circuit. Doing so can slow down how fast the contactor opens or closes, which may lead to weak or incomplete switching—and eventually welding.
Common suppression elements include:
- Diodes
- Capacitors
- Transistors
To work correctly, the contactor coil needs to have power applied and removed quickly—like flipping a switch, ideally within 1 millisecond. If the voltage ramps up or down slowly, actuation becomes sloppy. The same rule applies if you’re using PWM drive.
Always follow the coil drive specs exactly—for both closing the contactor and holding it closed.
-
Shock and Vibration
In rugged environments, shock and vibration can also lead to welding. A sudden jolt can cause the contacts to bounce open while current is flowing. This creates an arc, which can make a small hot spot. If the contactor then re-closes and that hot spot cools down and solidifies, the contacts can fuse.
It’s not common—but in harsh or mobile environments, it’s something to be aware of.
How to Open a Welded Contactor
If a contactor is lightly welded, there are a few tricks that might help free it up. As long as the contactor opens again and the insulation resistance is still within spec (usually over 10 MΩ), it can generally be reused.
Here are some common techniques:
- Tap: Sometimes just picking up the contactor and setting it down on a workbench is enough. The slight (or more forceful) jolt can break the contacts free.
- Rapid Cycling: You can also try switching the contactor on and off quickly—up to about twice per second. If the contactor doesn’t release after 50 cycles, the weld is likely more serious, and the contactor may need replacing.